Network of industrial pipes and valves
Systems, not just heaters

Process Heating

Complete heating loops: heater, controls, sensors, power switching and the heat balance behind them.

Closed-loop process heating system Reservoir Pump Circulation heater Process user Controller

Schematic illustration drawn for ECC, not to scale.

01Product description

Process heating combines heaters with the controls, sensors, power switching and piping needed to hold a process at temperature. Correct sizing starts from a heat balance of the process rather than from the heater catalog.

02Operating principle

Sizing follows three basic steps: determine the power needed to bring the process to temperature in the desired time; calculate the power needed to maintain it, covering losses; and select the number and type of heaters to supply that power.

03Industrial applications

  • Closed-loop heat transfer fluid systems
  • Process water and cleaning systems
  • Heating of tanks through external loops
  • Temperature maintenance of process lines

04Technical characteristics

  • Heaters sized from a documented heat balance
  • Temperature controllers and over-temperature limits
  • Power switching (contactors or solid-state relays/SCRs)
  • Sensors (thermocouples or RTDs) placed for control and protection
  • Control panels and electrical drawings

05Advantages

  • The whole loop is designed together
  • Better temperature stability and protection
  • Documentation for operation and maintenance

06Selection variables

  • Mass or flow of the material and its specific heat
  • Start and final temperatures, and heat-up time
  • Heat losses from surfaces, piping and openings
  • Safety factor for unknowns
  • Control accuracy and protection required

07Installation considerations

  • Separate the control sensor from the over-temperature limit sensor.
  • Size conductors and protection for the full heater load.
  • Commission with measured temperatures before continuous operation.

08Technical information

The heater must cover the heat-up of the material and the losses of the system, with a margin for unknowns.

Pheat-up (kW) = W × cp × ΔT ÷ (3,412 × t)
Ptotal = (Pheat-up + Plosses) × SF

Worked example

Heat 300 US gal of oil (SG 0.87, cp 0.47 Btu/lb·°F) from 70 °F to 250 °F in 3 hours. Estimated system losses at operating temperature: 2.5 kW. Safety factor 1.2.

W = 300 × 8.34 × 0.87 = 2,177 lb
Pheat-up = 2,177 × 0.47 × 180 ÷ (3,412 × 3) = 18.0 kW
Ptotal = (18.0 + 2.5) × 1.2 = 24.6 kW

The losses value in this example is an assumption for illustration; in a real project it comes from the insulation, surfaces and piping of the system. The heat-up estimator applies the first formula.

Request information on process heating

Share your application data; we will reply with the next steps and a quotation where possible.

Related technologies