Industrial cooling fans on a rooftop
ECC Thermal · Cooling

Air conditioning and refrigeration

The other direction of temperature: removing heat from spaces and processes. This branch is in development, starting in Costa Rica.

Branch in development

ECC Thermal is preparing its air conditioning and refrigeration offer, starting in Costa Rica. Scope, brands and services will be published when they are defined. Installation and maintenance must comply with local regulations and be carried out by qualified professionals.

Areas under evaluation

Where cooling fits in the ECC Thermal offer

Under evaluation

Comfort air conditioning

Cooling of commercial and industrial spaces: offices, plants and service areas.

Under evaluation

Process cooling

Removing heat from equipment and processes, for example with chilled water systems.

Under evaluation

Refrigeration

Cold rooms and refrigerated storage for commercial and industrial users.

Engineering basics

Sizing cooling: from airflow to tons

Cooling capacity is the heat removed per hour. These standard relations connect the common units:

1 ton of refrigeration (TR) = 12,000 Btu/h = 3.517 kW
Sensible heat of air: Q (Btu/h) = 1.08 × CFM × ΔT (°F)
Efficiency: COP = EER ÷ 3.412

CFM = airflow in cubic feet per minute. The 1.08 factor applies to standard air.

Worked example

Cool 2,000 CFM of air from 80 °F to 60 °F with equipment of EER 11:

Q = 1.08 × 2,000 × 20 = 43,200 Btu/h
= 43,200 ÷ 12,000 = 3.6 TR = 12.7 kW of cooling
Electrical input ≈ 43,200 ÷ 11 = 3.9 kW (COP ≈ 3.2)

This is the sensible load of the air only. A real cooling load also includes humidity (latent heat), people, lighting, equipment and solar gains, and must be calculated for the specific space.